久久艹一区二区I性孕妇free特大另类I久久一区I亚洲精品资源在线观看I冲田杏梨61部番号图片I在线视频区I色网站国产精品I97精品欧美91久久久久久I欧美老逼性生活69I欧美99999I吃奶爱爱I九七电影网97手机版不用播放器I不卡的av在线I精品福利视频在线Iwww.91n2I337p亚洲精品色噜噜狠狠网站I天天草天天摸I91精品国产综合久久久蜜臀图片

Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
CN EN

Vacuum interrupter for indoor circuit breaker TD435Y

Model:VITD24/1250-25

Category:VI for indoor circuit breakers

Product details

1.jpg
Main Technical Specification
VOLTAGE RATINGS
Rated voltage(Ur)kV24
Rated short-time(1min)power-frequency withstand voltage(Ud)kV65
Rated lightning impulse withstand voltage(Peak)(Up)kV125
Rated frequency(fr)Hz50
CURRENT RATINGS
Rated current(Ir)A630/1250
Circuit resistance at lowest rated contact forceμΩ≤20
Rated short-circuit breaking current(lsc)kA25
Breaking operations of rated short circuit breaking currentTimes30
Rated short-time withstand current(lk)kA25
Rated duration of short-circuit(tk)s4
Rated peak withstand current(lp)kA63
Rated short-circuit making current(lMc)kA63
Rated cable-charging breaking current(lc)A25
Rated breaking current of single capacitor bank(lsb)A400
Rated breaking current of back-to-back capacitor bank(lbb)A400
MECHANICAL DATA
Weight of movable partskg≤1.6
Closing force due to bellow and atmosphereN150±50
Force required to hold contacts open at full strokeN190±60
MECHANICAL REQUIREMENTS
Clearance between open contactsmm12±1
Average opening speed (contact close position~75%contact gap)m/s1.5±0.25
Average closing speed (30%contact gap-contact close position)m/s0.8±0.15
Rated added external contact final forceN3150±200
Added external contact force at contact touch point1600±100
Contact bouncing duration at closing operationms≤2
Closing and opening non-simultaneity of three-phase contactsms≤1
Maximum rebound during openingmm≤3
LIFE
Storage lifeyears20
Rated mechanical enduranceTimes10000
Contacts limit erosionmm3

Relevant information